Apc Symmetra Lx 16kva User Manual

APC Symmetra LX 16kVA Scalable to 16kVA N+1 Rack-mount, 208/240V. Rack Mounting support rails, Temperature Probe, User Manual, Web/SNMP Management Card.

Symmetra® LX

Start-Up Guide

Apc Symmetra Lx 16kva User Manual 2017

Extended Run Cabinets

For use with Symmetra LX UPS models:

200V, 4–8 kVA

200V, 4–16 kVA

208/240V, 4–8 kVA

208/240V, 4–16 kVA

220/230/240V, 4–8 kVA

220/230/240V, 4–16 kVA

READ FIRST

Important Safety and Installation Instructions

This guide is applicable for the Symmetra LX tower and rack-mount extended run cabinet models. These units provide extended run time for the Symmetra LX tower or rack-mount UPS models.

See and retain the product documentation shipped with your system for other important installation, operation, and maintenance instructions.

Illustrations are representative. The Symmetra LX configuration, including components and optional APC equipment, may be different from the models shown in this guide.

Entire contents copyright 2005 by American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited.

APC, the APC logo, InfraStruXure, PowerChute, Smart-UPS and Symmetra are registered trademarks of American Power Conversion Corporation. All other trademarks are the property of their respective owners.

9-Battery Rack-mount Extended Run

3-Battery Rack-mount Extended Run

9-Battery Tower Extended Run

990-1873-001 04/2005

Overview

1. Read Safety and General Information Instructions

Read, understand and follow ALL safety instructions contained in the Symmetra LX Safety

Instructions and General Information Guide.

Electrical

Failure to follow safety instructions and warnings

Hazard

could result in equipment damage, serious injury,

or death.

2. Refer to the UPS Documentation

If installing the Symmetra LX and the Extended Run Cabinet(s), install according to the instructions in the Symmetra LX Start-Up Guide shipped with the UPS.

3. Install the Extended Run Cabinet(s)

Perform the physical installation for the extended run cabinet(s). See the included Symmetra LX Physical Installation Guide.

4. Follow the proceeding Start-Up Instructions

See these instructions once the physical installation for the Extended Run Cabinet(s) is complete. This section contains information on how to connect, test, and start the unit.

Start-Up Instructions

The illustrations shown in this section are applicable for the

tower and rack-mount extended run cabinets.

Note

1.Connect the first Extended Run Cabinet

1.1Remove the screw and battery connector cover from the back of the UPS.

1.2Connect the power cable of the first extended run cabinet to the UPS battery connector .

1.3Set the dial of the extended run cabinet to ‘2’.

If connecting to a UPS with integrated extended run, set the

dial of the first extended run cabinet to ‘3’ instead of ‘2’.

Note

1.4Connect the communications cable from the extended run communications connector on the UPS to the connector on the extended run cabinet .

2. Connect additional Extended Run Cabinets

Connect each additonal extended run cabinet to the previously installed cabinet. The Symmetra LX supports a maximum of seven cabinets.

2.1Remove the screw and UPS battery connector panel from the previously installed cabinet.

2.2Connect the power cable from the new cabinet into the battery connector of the previous cabinet.

2.3Set the dial of the new cabinet to a number that is one higher than that of the previous cabinet .

2.4Connect the communications cable from the communications connector of the new cabinet to that of the previous cabinet .

16kva

3. Verify Connection

• To verify the connection, the UPS must be on. For further information, see the Symmetra LX Start-Up Guide.

Apc symmetra lx

Note • Messages regarding battery quantity may be visible on the UPS PowerView display.

3.1Check that the green status light on the rear of each cabinet will light.

3.2Check that the front display shows the correct dial number.

3.3Refer to the status menu on the UPS PowerView display (see the Symmetra LX Operations Guide) to verify that the number of battery modules matches the total number of battery modules installed in the UPS and all extended run cabinets. Also, verify there are no bad battery modules present.

Troubleshooting

It is assumed that the Symmetra LX is powered and functioning during these startup procedures. If the problem persists, call technical support. Visit the the APC website at http://www.apc.com/support for contact information.

Problem

Possible Cause

Solution

The green status LED (rear

There is no battery power

Check that the battery cable

of frame), and the front

present at the frame.

and battery modules are

properly installed.

display (front of frame) do

not light after the

The communication cable is

Check that the

communication cable is

not installed

communication cable is

installed.

properly installed.

The display cable is not

See the Extended Run

The green status LED

connected.

Cabinet Physical Installation

Guide for proper cable

lights, but the front display

connection instruction.

does not show the frame

number.

There is a potential hardware

Call technical support.

failure.

The front display

More than one frame is set

Check that frame numbers

continuously flashes on

with the same frame number.

are not duplicated on the

and off.

communication card(s).

The “E_O” frame error code

Check that the battery cable

may indicate that the battery

is properly installed. If the

cable is not installed.

error code continues to flash,

call technical support.

An “XR frame failure” is

The “E_7” frame error code

Check that the

may indicate that the

communication cable is

reported. The front display

communication cable is not

properly installed. If the error

flashes an error code.

installed

code continues, call

technical support.

All other LED error codes

Call technical support and

could indicate a potential

report the error code.

hardware failure.

The front display

A failed battery module has

Replace the battery module.

alternately flashes the

been detected in the location

To obtain a replacement

frame number and either

displayed.

battery, see the APC

“Lx” , “Cx”, or “Rx”.

website.

One or more battery module

Check that the disconnect

disconnect switches are off

switch on all modules is

The number of battery

(opened).

closed (counter-clockwise).

modules reported is

Battery modules are not

Check that all battery

inaccurate.

installed correctly.

modules are properly

installed in the extended run

frame(s).

To continue the download you need to go through the captcha:

3-16kVA Service Bypass Panels

©2009 APC by Schneider Electric, APC, the APC logo, and Smart-UPS are owned by Schneider Electric industries S.A.S American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.

990-1530B

Note: Read the safety information sheet before installation.

Illustrations in this document may differ slightly from the actual hardware.

Attention: This product is for use in a controlled environment. Refer to product specifications for environmental limits.

RACK MOUNTING

n

x4

x8

x2

oSet SBP in the rack. If hardwiring is required, see Connecting Power section before screwing into the rack.

x4

WALL MOUNTING

n

x8

oWhenever possible, attach one top screw and one bottom screw into a wall stud. If stud mounting is not possible, use an expandable wall anchor. Screws are not included; .25” x 2” lag bolts are recommended.

x4

TOWER OPTION (FOR SMART-UPS RT SETUPS ONLY)

n Remove screw from the top and bottom rear of both the UPS and SBP. Install tie brackets and reattach screws.

Front

Rear

x4

x2

Apc Symmetra Lx Installation Manual

oUnscrew and remove top cover of the pAttach bracket to top of UPS and SBP. UPS.

x2

x1

qReattach top cover of the UPS.

Note: The SBP5000RMI2U, when used in conjunction with an SURT3000XLI or SURT5000XLI UPS in a tower configuration without an external battery pack (SURT192XLBP), is suitable for mounting on concrete or other non-combustible smooth surfaces only.

USER CONFIGURABLE

Attention: When using an online UPS, put the UPS in automatic bypass mode before rotating the SBP switch.

1.Normal: Power is directed from the utility outlet, through the Bypass Panel and UPS, and to connected equipment. For use during normal UPS operation.

2.Test: Power supplied to the UPS is not output. Use when tests are being conducted on the UPS, and connected equipment is not yet desired.

3.Bypass: Power from the utility outlet is filtered through the Bypass Panel, and to the connected equipment. Use to bypass the UPS, when functioning improperly.

Note: While operating in ‘Test’ or ‘Bypass’ mode, power to the connected equipment is not conditioned by the UPS. At this time, the “Equipment Protection Policy” is not valid.

IDENTIFYING THE PANEL

Service Bypass Panels will differ. Refer to chart for unit specifications. Note: HW= Hardwire

Apc Symmetra Lx

Service Bypass

Corresponding

Bypass

UPS

UPS

PDU

Panel

UPS Systems

Input

Input

Output

Panel

SBP3000RM2U

100-120V Smart-UPS

L5-30P

L5-30R

L5-30P

(2) 5-20R,

3kVA

(6) 5-15R

SBP5000RMT2U

200/208/240V

L6-30P

L6-30R

L6-30P

(2) L6-20R,

Smart-UPS 3-4.5kVA

(2) L6-30R

SBP5000RMI2U*

230V Smart-UPS

C20/HW

C19/HW

C20/HW

(2) C19,

3-5kVA

(8) C13

SBP6KRMT2U**

200/208/240V

L6-30P/

L6-30R/

L6-30P/

(1) L6-20R,

Symmetra 2-6kVA

HW

HW

HW

(2) L6-30R

SBP6KRMI2U

230V Symmetra

HW

HW

HW

(4) C19

2-6kVA

SBP3000

100-240V Smart-UPS

HW

HW

HW

HW

3-5kVA with 30A HW

input/output

available

SBP10KRMT4U

200/208/240V

HW

HW

HW

(3) L6-20R,

Smart-UPS RT

(3) L6-30R

7.5-10kVA

SBP10KRMI4U

230V Smart-UPS RT

HW (3Ph

HW (3Ph

HW

(8) C13,

7.5-10kVA

or 1Ph)

or 1Ph)

(2) C19

SBP16KP

200-240V

HW (3Ph

HW (3Ph

HW

HW

Symmetra LX

or 1Ph)

or 1Ph)

4-16kVA

SBP16KRMI4U

220-240V

HW (3Ph

HW (3Ph

HW

(3) 30A HW

Symmetra LX

or 1Ph)

or 1Ph)

4-16kVA

SBP16KRMP4U

200/208/240

HW

HW

HW

(6) L14-30R

Symmetra LX

4-16kVA

SBP16KRMP4U-HW

200/208/240

HW

HW

HW

(1) L14-30R,

Symmetra LX

(3) L5-20R,

4-16kVA

(1) 100A HW

*For loads exceeding 3kVA, hardwiring is necessary.

**For loads exceeding 5kVA, hardwiring is necessary.

CONNECTING POWER

Apc Symmetra Lx 16kva User Manual Download

Warning: Do not modify inlets or outlets. The SBP and UPS plugs and receptacles should match. For more information, contact APC.

1.Non-Hardwired Panels

1.Plug SBP UPS output cord into UPS PDU panel.*

2.Plug UPS input cord to SBP UPS input receptacle.*

3.Plug customer equipment into SBP PDU panel.

4.Plug SBP into utility power outlet.

*Units with IEC receptacles: Use jumper cables.

2. Hardwired Panels

Attention: Wiring must be performed by a qualified electrician.

1.Switch input circuit breaker off.

2.SBP units that will be rack-mounted: Set SBP in the rack.

3.Unscrew and remove top access panel.

4.If using SBP5000RMI2U or SBP6KRMT2U with a hardwired UPS: Unscrew existing terminal block wiring. Do not touch factory wiring (see E).

5.If using SBP5000RMI2U or SBP6KRMT2U with a hardwired UPS: Unscrew and remove rear input/output panel.

Apc Symmetra Lx 16kva User Manual 2016

6.Remove circular knockouts from hardwiring input/output panel (see A, B, C, D: UO= UPS Output; UI= UPS Input; AI= AC Input; LD= Load).

SBP3000 units: Also, remove PDU output panel knockout plate.

SBP16KP units: Also, remove circular knockouts from PDU output panel.

7.Connect wires to terminal blocks (see E, F, G, H, I). Adhere to all national and local electrical codes.

8.Reinstall access panel.

9.Install hardwiring input/output panel.

10.SBP units that will be rack-mounted: Screw SBP into the rack.

A.

B.

C.

D.

E. 2U PANELS

F. SBP10KRMT4U

G. SBP16KRMP4U, SB16KRMP4U-HW

Apc Symmetra Lx Ups

H. SBP16KP

I. SBP10KRMI4U, SBP16KRMI4U

TROUBLESHOOTING

Use the chart below to solve minor SBP installation problems. Also, refer to the UPS User Manual Troubleshooting section. For more complex issues, refer to www.apc.com.

Apc Symmetra 16kva Ups

Problem and

Solution

Possible Cause

UPS WILL NOT TURN ON AFTER ON BUTTON IS PUSHED

SBP handle is in ‘Bypass’ position.

Rotate the SBP handle to the ‘Normal’ position.

There is no power at UPS input.

Check that the power cables from the SBP to the utility power, and

from the SBP to the UPS Input are securely connected.

UPS is faulty or damaged.

Rotate the SBP handle into the ‘Test’ position. If the connected

equipment becomes energized, the UPS may be faulty. To confirm

this, refer to UPS User Manual Troubleshooting.

There is no power at the utility

Rotate the SBP handle into the ‘Test’ position. If the connected

power outlet.

equipment fails to become energized, the utility power outlet may be

faulty. Check the utility power supply by plugging a table lamp into

the suspect outlet. If the utility outlet fails to power the lamp, contact

qualified service personnel to restore power.

UPS IS ONLINE; NOT POWERING ALL CONNECTED EQUIPMENT

SBP output circuit breaker tripped.

Reduce the load by unplugging equipment. Reset the breaker.

There is no power at SBP output.

Check that the power cable from the SBP to the UPS output is

securely connected.