End User
- Ariston Microgenus 23 Mffi Installation Manual
- Ariston Microgenus 23 Mffi User Guide
- Ariston Microgenus 23 Mi Manual
- Ariston Microgenus 23 Mffi Service Manual
- Ariston Microgenus 23 Mffi User Manual Instructions
- Ariston Microgenus 23 Mffi User Manual Pdf
Listed below are all the manuals for Ariston. Just click on the model or the Gas council number and the manual will download at the bottom of the page. After you have downloaded the manual double click on the download for the manual to open, if you want to save the download right click. Ariston microGENUS HE 24 MFFI Manuals & User Guides. User Manuals, Guides and Specifications for your Ariston microGENUS HE 24 MFFI Boiler. Database contains 2 Ariston microGENUS HE 24 MFFI Manuals (available for free online viewing or downloading in PDF): Installation and servicing instructions, Operation & user’s manual.
Manual
microGENUS II 24 MFFI microGENUS II 28 MFFI microGENUS II 31 MFFI
I
2
1
Dear Customer,
Thank you for choosing an ARISTON boiler.
We guarantee that your boiler is a reliable and technically sound product. This manual provides detailed instructions and recommendations
for proper installation, use and maintenance.
Remember to keep this manual in a safe place for future reference i.e. by the gas meter.
Your local MTS Servicing Centre is at your complete disposal for all requirements.
The guarantee on this appliance is valid for 24 months from the first day of installation.
Repairs to the electric, hydraulic or gas circuits may be carried out only by your local authorised MTS Servicing Centre.
Every attempt has been made to avoid errors of any kind in this manual, the Management invites customers to inform of any inaccuracies which they may find.
This will help to improve our service
TABLE OF CONTENTS
1. | GENERAL INFORMATION | page | 2 |
Control Panel | page | 3 | |
2. | OPERATING INSTRUCTIONS | page | 3 |
3. | USEFUL INFORMATION AND TROUBLESHOOTING | page | 5 |
4. | MAINTENANCE | page | 6 |
5. | CHANGE OF GAS TYPE | page | 6 |
6. | MECHANICAL TIME CLOCK | page | 6 |
7. | Digital Programmer | page | 7 |
IMPORTANT!
Please read this manual carefully.
For additional information, please consult the “Installation and Servicing Instructions.” Make sure to keep the manuals provided with the appliance so that they can be used by the end-user, installer or our authorised engineer.
1. GENERAL INFORMATION
MTS (GB) Limited support the initiative. Your installer will give you, and show you how to use, a Log Book which will give you important information about your boiler, and heating system. Please have this Log Book to hand whenever you contact a service engineer or us.
All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded in your boiler Logbook. You can check your installer is CORGI registered by calling CORGI direct on :- (01256) 372300.
This is a combined appliance for the production of Central Heating (C.H.) and Domestic Hot Water (D.H.W.). This appliance must be used only for the purpose for which it is designed. The manufacturer declines all liability for damage caused by improper or negligent use.
Do not allow children or inexperienced persons to use the appliance without supervision. If you smell gas in the room, do not turn light switches on or off, use the telephone or any other object which might cause sparks.
Open doors and windows immediately to ventilate the room.
Shut the gas mains tap (on the gas meter) or the valve of the gas cylinder and call your Gas Supplier immediately.
If you are going away for a long period of time, remember to shut the mains gas tap or the gas cylinder valve.
Before any intervention within the boiler it is first necessary to isolate the electrical supply by turning the external switch to “OFF”.
CONTROL | PANEL | I | J | K |
E | C | |||
I | ||||
3 | 4 | |||
3 | 4 | 2 | 5 | |
2 | 1 | |||
5 | 6 | |||
1 | 6 |
LEGEND:
A - On/Off Switch
B - Domestic Hot Water Temperature Adjustment
C - Central Heating Temperature Adjustment
D - Reset Button
E - Comfort Mode Selector
F- Hot Water (Summer Mode LED - Green)
G- Ignition/Overheat Lockout LED (Red)
H- Central Heating (Winter Mode) LED (Green)
I- Digital Display (Fault Code/Water Temperature)
J- Time Clock
K-Central Heating System Pressure Gauge
CAUTION
In the United Kingdom installation, start-up, adjustments and maintenance must be performed by a CORGI Registered Installer in accordance with the installation standards currently in effect, as well as with any and all local health and safety standards i.e.. CORGI.
In the Republic of Ireland the installation and initial start up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Building Regulations, reference should also be made to the current ETCI rules for electrical installation.
HELPFUL SUGGESTIONS
To get the most out of your boiler, we have provided you with some useful advice on proper use and maintenance:
-Periodically check the system pressure using the pressure gauge “D”, make sure that the pressure is at 1.5 bar when the system is off and cool. If the pressure is below the minimum recommended value (1 bar). To refill the system, open the two black handles connected to the silver flexible hose, once the pressure gauge “K” reads 1.5 bar close the valves again.
NOTE: DO NOT UNDER ANY CIRCUMSTANCES USE THE APPLIANCE WITH THE PRESSURE GAUGE READING ZERO.
-The outer panels of the unit's case must only be cleaned with a damp cloth. Do not use abrasive cleaners. The control panel can be wiped with either a damp or dry cloth. Spray polishes must not be used on the control panel surface or knobs. Care must be taken to prevent any liquid from entering the appliance.
PRACTICAL TIPS
-If the water is very hard, it is recommended that a water softener be added to the system so as to reduce the formation of limescale in the boiler exchangers. This will
M | N |
PL004D
PL007D
summer
PL009D
winter
PL009D
C
3 | 4 |
2 | 5 |
1 | 6 |
PL008D
C | 3 | 4 |
2 | 5 | |
1 | 6 |
PL008D
B | 4 |
3 | |
2 | 5 |
1 | 6 |
ensure that the efficiency of the unit remains the same over time, reducing gas consumption and maintenance costs.
-If the boiler should be out of use for a prolonged period, it is recommended that the electrical power supply be disconnected and that the external gas cock “M” and “N” be closed. If low temperatures are expected, the boiler and system pipe work should be drained in order to prevent frost damage.
-To improve comfort and take full advantage of the heat produced by the boiler, it is recommended that an external (room) thermostat be installed.
-It is good practice to clean and service the appliance and central heating system every year. Call an Authorised Service Centre.
IGNITION PROCEDURE
Turn the selector knob “A” to the “I” position. After a short delay the display will indicate “on” indicating that the boiler is ready to operate. The electronic control unit will ignite the burner, without any manual intervention but in response to the request for Domestic Hot Water or Central heating. If, after approximately 10 seconds, the burner has not ignited,
the boiler safety devices will shut off the gas and the display will | ||||
indicate the fault code A01. To reset the ignition system, the reset | A | I | ||
button “D” must be pressed and released. Should the boiler fail to | ||||
ignite a second time, check that the external gas cock is open “N”. | ||||
If the problem persists, contact an Authorised Service Centre. | ||||
WINTER AND SUMMER | OPERATING MODES | PL004D | ||
In the ‘winter’ operating mode, the | boiler will produce both Central | |||
D | ||||
Heating and Domestic Hot Water. In the ‘summer’ operating mode, the | PL006C |
boiler will produce only Domestic Hot Water.
Using the knobs on the control panel, the user can select ‘winter’ or ‘summer’ operating mode.
Keeping the knob “C” at the “ ” position selects the ‘summer’ | summer | ||
operating mode, the symbol “ “ will illuminate. ‘Winter’ operating | 3 | 4 | |
mode may be selected by positioning the knob “C” between the | 2 | 5 | |
min. and max. settings. The symbol “ | “ will illuminate. |
ADJUSTING THE HEATING
It is possible to set the temperature of the Central Heating system by adjusting the knob “C”. By positioning the indicator somewhere between min. and max., a temperature may be obtained which varies from approximately 42˚C to about 82˚C.
The water temperature in the Central Heating circuit may be checked on the display.
EXTERNAL (ROOM) THERMOSTAT CONTROL
If an external (room) thermostat is installed, it is recommended that the temperature of the Central Heating system be set by means of the “C” knob, leaving it at max in order to obtain the best performance from the boiler and to allow the regulation of the external temperature to function efficiently.
SETTING THE HOT WATER FOR DOMESTIC USE
Both in the winter and summer mode, the temperature of the Domestic Hot Water may be adjusted by using the “B” knob. A delivery temperature for the water may be chosen in a range from 36˚C to about 56˚C, depending on the flow rate of the water and the position of the knob between the min. and max. settings.
The water temperature in the primary circuit may be checked on the display.
NOTE: Should the hot water temperature be insufficientm turn the thermostat knob to maximum and reduce the flow rate at the tap. ( A high flow rate will reduce the temperature.
ECONOMY/COMFORT MODE | ||
E | C | The selector knob “E” allows the user to choose the economy mode (position “E”) or the |
comfort mode (position “C”). | ||
The economy mode is the normal state for the operation of the boiler, since the domestic | ||
water is heated up only when a tap is turned on. | ||
confort | The comfort mode is a special operating state, because the water contained in the | |
PL006D | ||
secondary exchanger and in the primary exchanger is kept in a pre-heated condition, | ||
thereby allowing a quicker delivery of Domestic Hot Water when required. | ||
4 | ||
5 | TURNING OFF THE CENTRAL HEATING | |
6 |
PL008D
A I
PL004D
3.USEFUL INFORMATION AND TROUBLESHOOTING
To turn off the Central Heating, rotate the “C” knob to the “ ” position.
The boiler will stay in ‘summer’ mode, providing Domestic Hot Water on request.
TURNING OFF THE BOILER
To turn the boiler off, rotate the selector knob “A” to the “0” position (OFF); the display will go off. Close the gas cock located under the boiler and turn the electricity supply switch (located outside the boiler) to the OFF position.
BOILER SHUTDOWN SITUATIONS
The boiler is equipped with safety devices that intervene in certain situations and shut it off. Most of these situations are signalled by means of the L.E.D.s and in some circumstances the user may be able to remedy them.
SHUTDOWNA 01 DUE TO IGNITION FAILURE
This anomaly is indicated by “ ” on the display. To reset the boiler, press and then release button “D”.
At this point, the electronic ignition system will attempt to light the burner again.
Should the boiler fail to ignite a second time, check that the external gas cock is open. If the problem persists, contact an Authorised Service Centre.
SHUTDOWNA 03 DUE TO OVERHEATING
This anomaly is indicated by “ ” on the display. The boiler has shutdown because the safety thermostat detected that the boiler temperature has exceeded the maximum limit.
To reset, wait until the boiler has cooled and press button “D”.
If the safety thermostat operates on a frequent basis, contact one of our Authorised Service Centres.
SHUTDOWN DEUE02TO INSUFFICIENT WATER CIRCULATION
This anomaly is indicated by “ ” on the display.
One of the possible causes of this shutdown situation could be the lack of water in the boiler or water circulation failure in the primary heating circuit.
Check the system pressure on the pressure gauge “K” and, if it K is less than 0.5 bar, try bringing the system pressure up to a
mean value of 1.0 bar by opening the water inlet valve as instructed on page 3. Then reset by pressing button “D”.
OTHER SHUTDOWN SITUATIONS
Should a shutdown situation indicated on the display by the following letters and figures occur, E04, E05, E06, E07, E08, E09, E20, E33, E34 contact one of our Authorised Service Centres.
4.MAINTENANCE
5.CHANGE OF GAS TYPE
6. MECHANICAL TIME CLOCK
UT011Ap
If instead the display shows one of the shutdown situations indicated by the following letters and figures, A64, A97, A98, A99, try resetting the boiler by pressing the reset button “D”. If the boiler shuts off again, contact one of our Authorised Service Centres.
ANTI-FROST DEVICE
The boiler is fitted with a device which, in the event that the water temperature falls below 8˚C the pump activates and runs until a temperature of 18˚C is attained. In the event that the water temperature falls below 3˚C, the diverter valve switches to Domestic Hot Water and the burner fires and runs on minimum power until a temperature of 33˚C is attained. This device is only activated when the boiler is operating perfectly and
-the system pressure is sufficient;
-the boiler is powered electrically;
-gas is being distributed.
Schedule an annual maintenance check-up for the boiler with a CORGI registered Service Engineer.
Correct maintenance always results in savings in the cost of running the system.
Our boilers are designed to function either with Natural Gas (methane) or L.P.G. gas. If you need to changeover from one gas to the other, one of our Authorised Service Centres should be contacted.
NOTE: the time clock is for central heating control only.
The time clock is provided with 96 switches, called riders, each of which covers a time interval of 15 minutes (four per hour).
When a rider is switched from the inside (off setting) to the outside of the clock border (on setting), the circuit is closed (switch on) for a period of 15 minutes and then the boiler starts if the room thermostat (if installed) or the heating thermostat require heat (heating function on).
EXAMPLE
To set the heating of your home in the time interval from 7.00 am to 9.30 am and from
7.00 pm to 10.00 pm every day:
-rotate the outer ring of the clock in a clockwise direction until the correct time of day (24h) lines up with the arrow on the clock (at approx. 2 o’clock position);
-under no circumstances should the minute hand be moved manually;
-make sure all the switches, i.e. the riders, are placed on the inside of the clock border;
-pull outward the riders for 7.00 am and 9.30 am, and then all riders between these two;
-repeat this for 7.00 pm and 10.00 pm.
Other heating intervals may be set in the same way.
The timer has approximately 150 hours of battery back up for power failure.
The clock is provided with a selector switch with three positions (see figure):
1. Position “I” CONSTANT: in this position, the clock circuit is always closed (switch on), therefore the boiler will constantly be on and will only shut off upon the request of the room thermostat (if installed) or the heating thermostat;
UT014A
2. Position “O” HEATING OFF: in this position, the clock circuit is always open (switch off) and the boiler will therefore never ignite for heating;
UT014A
3. “Central” Position PROGRAMMING ACTIVE: in this position, the programming set by the user is active.
UT014A
7. DIGITAL PROGRAMMER | ||||||
Manual switch | ||||||
Summer and | ||||||
winter time | Automatic | Manual | Continuous | |||
Reset | setting | Operation | Operation | Operation | ||
= ON | = ON | = Continuously ON | ||||
Enter | Enter | = OFF | = OFF | = Continuously OFF | ||
switching | the hours | |||||
times | . | |||||
g | h | |||||
o | ||||||
r | The switching | If the current | You can only | |||
P | Week- | |||||
times corres- | switching mode is | return to automatic | ||||
days | ||||||
flash | pond to the | changed manually, | mode from the | |||
Imput | m | Enter | program | the next switching | continuously-ON | |
entered. | time will be | and continuously- | ||||
time | minutes | |||||
carried out auto- | OFF | switching | ||||
Day | matically again | modes by | ||||
according to the | pressing the ' | ' | ||||
entered switching | key. | |||||
program. | ||||||
Enter | ||||||
weekday/s | ||||||
Operating the time switch |
The step marked with the symbol “” are necessary to carry out a switching program.
Preparing for Operation
Activate the “Res” switch (=RESET) to reset the time switch to its default setting (activate using a pencil or similar pointed instrument). Do this:
-every time you wish to “reset” the time switch
-to erase all switching times and the current time of day.
After approximately two seconds the following display appears:
Enter current time and weekday
- Keep the “” key pressed down
During the summer time period press the +/- 1h key once. Enter the hour using the “h” key
Enter the minutes using the “m” key Enter the day using the “Day” key 1 = “Monday”..............7 = Sunday
- Release the “” key.
Entering the switching times
You have 20 memory Iocations available. Each switching time takes up one memory location.
Keep pressing the “Prog” key until a free memory location is shown in the display “– –:– –”.
Programme ON or OFF with the “ ” key: “”= OFF; “ ”= ON
Ariston Microgenus 23 Mffi Installation Manual
Enter the hour using “h” Enter the minutes using “m”
If a switching command is to be carried out every day (1 2 3 4 5 6 7) then store using the “ ” key, otherwise select the day(s) it is to be carried out by using the “Day” key.
When the day seIection is left bIank, the programmed switching
instruction operates at the | same time every day | |
1 2 3 4 5 6 = Monday – Saturday | ||
1 2 3 4 5 | = Monday – Friday | |
6 7 | =Saturday – Sunday |
Selection of single days: 1 = Mon. .............. 2 =Tues. Save the switching time with the “ ” key.
The time switch enters the automatic operating mode and displays the current time of day.
Begin any further entry of a switching time with the “Prog” switch. If your entry is incomplete, the segments not yet selected will blink in the display. After programming is completed, and you return the time clock to the current time display with the “ ” key, the time clock will not activate any switching instruction required for the current time. You may need to manually select the desired switching state with the “ ” key. Thereafter, as the unit encounters further switching instructions in the memory in real time, it will correctly activate all subsequent switching instructions.
Manual Override Switch “ ”
With the “ ” you can change the current setting at any time. The switching program already entered is not altered.
Reading the programmed switching times
Pressing the “Prog” key displays the programmed switching times until the first free memory location appears in the display “– – : – –”.
If you now press the “Prog” key once again, the number of free memory Iocations will be displayed, e.g. “18”. If all memory locations are occupied, the display “00” appears.
Changing the programmed switching times
Press the “Prog” key repeatedly until the switching time you want to change is displayed. You can now enter the new data. See point “Entering the switching times”.
Notes on storing switching times:
Ariston Microgenus 23 Mffi User Guide
If you end your entry of the switching times by pressing the “Prog” key, then the switching time you have entered will be stored and the next memory location displayed.
In addition, a complete switching command is stored automatically after around 90 seconds provided no other key is pressed. The time switch then enters the automatic operating mode and displays the current time again.
Deleting individual switching times
Ariston Microgenus 23 Mi Manual
Press the “Prog” key repeatedly until the switching time you wish to delete is shown in the display. Then set to “– –” using the “h” or “m” key and keep the “ ” key pressed down for around 3 seconds. The switching time is now erased and the current time is displayed.
AM / PM time display
If you press the “+/-1h” and “h” keys at the same time, the time display switches into the AM/PM mode.
Manufacturer: | Merloni TermoSanitari SpA - Italy | |
Commercial subsidiaries: | MTS (GB) Limited | MTS Heating Limited |
MTS Building | Damastown Industrial Park | |
Hughenden Avenue | Damastown Avenue | |
High Wycombe | Mulhuddart | |
Bucks HP13 5FT | Dublin 15 | |
Telephone: (01494) 755600 | Telephone: (01) 810 3723 | |
Fax: (01494) 459775 | Fax: (01) 810 3727 | |
Internet: www.mtsgroup.com/uk | Internet: www.mtsgroup.com/ie | |
E-mail: info@uk.mtsgroup.com | E-mail: info@ie.mtsgroup.com | |
Technical Advice: 0870 241 8180 | Technical Advice: (01) 437 0121 | |
Customer Service: 0870 600 9888 | Customer Service: (01) 437 0121 |
Boiler Manuals for the Ariston Microgenus 23 MFFI appliance. You have chosen to download this manual. Ariston Micro Genus 23 MFFI From , please click on the PDF link below. Listed below are all the manuals for Ariston. Just click on the model or the Gas council number and the manual will download at the bottom of the page. After you.
Author: | Zulkizragore Zurisar |
Country: | Turkey |
Language: | English (Spanish) |
Genre: | Marketing |
Published (Last): | 25 September 2018 |
Pages: | 303 |
PDF File Size: | 5.86 Mb |
ePub File Size: | 15.52 Mb |
ISBN: | 328-4-47149-478-1 |
Downloads: | 3715 |
Price: | Free* [*Free Regsitration Required] |
Uploader: | Dugis |
Table of contents R Eference S Tandards Please have this Log Book to hand whenever you contact a service engineer or us. Removing The Air Pressure Switch In order to save this manual manuak your online services account please log in or register for an account. View your documents Cancel. Got it, continue to print. E Lectrical C Onnection To print the manual completely, please, download it.
Ariston microCombi 23 MFFI End User Manual
Enter text from picture: Page of 24 Go. Fault Finding Guide flow – Chart Removing The Fan Removing The Gas Valve This will ensure that the efficiency of the unit remains the same over time, reducing gas consumption and maintenance costs. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps. Removing The Burner And Jets Regulations and applicable local regulations.
Access To The Control System Remember to keep this manual in a safe place for future reference i.
Ariston Microgenus 23 Mffi Service Manual
Ariston microGENUS 23 MFFI Installation Instructions Manual
Removing The Overheat Thermostat About us Contact us Emergencies. Removing The Pressure Gauge Table of contents Table Of Contents Useful Information And Troubleshooting Useful Information And Troubleshooting 3. Table of contents Servicing Instructions Add to my manuals Add.
This saves the selected manual if you have an online services account. Table Of Contents Removing The Electrodes Save to your online account What’s this? Got it, continue to print.
Don’t have an account? Jump to main content My Home My Business. Microgenus 27 mffiType cMicro genus type c. Comments to this Manuals Your Name.
Ariston Microgenus 23 Mffi User Manual Instructions
Boiler Manuals: Ariston Microgenus 23 MFFI
The diagrams for the electrical system are indicated in section 2. This manual provides detailed instructions and recommendations for proper installation, use and maintenance. We use cookies to provide a better experience. Twitter YouTube Facebook Latest news.
Ariston microGENUS 23 MFFI Manuals
Removing The Pump Your installer will give you, and show you how to use, a Log Jicrogenus which will give you important information about your boiler, and heating system.
Change Of Gas Type Removing The Expansion Vessel When a rider is switched from the inside off mcirogenus to the outside of the clock border on settingthe circuit is closed switch on for a period of 15 minutes and then the boiler starts if the room thermostat if installed or the heating thermostat require heat heating function on.
Ariston Microgenus 23 Mffi User Manual Pdf
The appliance has a built-in automatic air release valve, however it should be ensured as far as possible that the appliance heat exchanger kffi not a natural collecting point for air. Removing The Time Clock In addition, it is also possible to use a split twin pipe system by fitting a special adaptor to the flue connector and using the aperture for the air vent intake located on the top part of the combustion chamber.
By pressing ‘print’ button you will print only current page. Removing The Spark Generator